DaytonHazardous Location Direct-Drive Exhaust Fans

Dayton hazardous location exhaust fans are designed for ventilating spaces containing flammable or explosive vapors, gases, or dusts as defined under Article 500 of the National Electrical Code (NEC). Mount in vertical or horizontal position. Construction includes galvanized steel frame and finish, pre-punched mounting holes, hazardous location ball bearings, and spark-resistant aluminum propeller.

  • Galvanized steel fan panel with one-piece, drawn venturi
  • Maximum inlet air temperature: 104º F
  • Prepunched panel
  • UL/cUL Listed Standard 1203, NEC Class I, Division I, Groups C and D; NEC Class II, Division I, Groups F and G

Agency Compliance

Performance

Not Applicable

Motor HPMax BHPFan RPMCFM @
0.000'' SP0.125'' SP0.250'' SP0.375'' SP0.500'' SP
1/4
1750
CFM
Sones
0.000'' SP0.125'' SP0.250'' SP0.375'' SP0.500'' SP
134712621142947604
13.413.413.614.216.4
Agency Compliance

Dayton Electric Mfg. Co. certifies that the fans shown herein are licensed to bear the AMCA seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 and comply with the requirements of the AMCA Certified Ratings Program.

Performance certified is for installation type A: Free inlet, Free outlet. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: Free inlet hemispherical sone levels.

Product Specifications (Glossary)

Agency Compliance [?]
  • AMCA Sound & Air
  • UL/cUL 1203
  • CSA Certified Motor
Assembled [?]TRUE
Bearing Type [?]Ball
CFM [?]604 to 1,347 ft3/min
Depth [?]12 1/2 in
Drive Type [?]Direct Drive
Fan DescriptionExhaust Fan
Frame Material [?]Galvanized Steel
Full Load Amps [?]1.4-1.3/0.7
Height [?]16 in
Hertz (Cycle) [?]60 Hz
Horsepower (Typ.) [?] 1/4 hp
Housing Material [?]Galvanized Steel
Impeller Diameter (Nom.) [?]12 in
Impeller Material [?]Cast Aluminum
Impeller Type [?]Propeller
Includes [?]Hazardous Location Motor
Max Inlet Temp [?]104 °F
Motor Enclosure [?]Explosion Proof Fan-Cooled
Motor IncludedYes
Motor Insulation [?]B
Motor Phase [?]3
Motor Type [?]
Mounting Location [?]
  • Wall
  • Ceiling
Motor Nominal Efficiency %
Number of Blades [?]5
RPM [?]1,750 rpm
Shaft Diameter [?] 5/8 in
Speed Controllable [?]No
TypeDirect-Drive Hazardous Location, Panel
Voltage [?]208-230/460
Warranty Length [?]1 Year
Width [?]16 in