Download PDF for Print 5/18/2024

Centrifugal Belt-Drive In-Line Duct Blower

Item

Designed for indoor clean air applications including intake, exhaust, return, or make-up air systems in industrial or commercial buildings. Rugged construction allows fan to be installed in ductwork either horizontally or vertically. Duct collars provide easy duct connections. Access panels are included on each side of the unit.

  • Aluminum backward inclined, nonoverloading centrifugal wheel design
  • UL/cUL 705 Listed for Power Ventilators
  • Maximum inlet air temperature: 160º F
  • Bearing and motor cover provide longer service life
  • Sealed pillow block bearings
Item
ABCD
15 in21 in11 7/8 in1 in
EFG
17 3/8 in16 in12 1/2 in

Performance Characteristics

Item

Construction Features

Impeller Diameter (Typ.)11 in
Impeller TypeBackward Inclined Centrifugal
Impeller MaterialAluminum
Max Inlet Temp160 °F
Bearing TypeSealed Pillow Block
Drive Package DescriptionDrives By Others
Warranty Length1 Year

Air & Sound Performance

Motor HPMax BHPFan RPMCFM @0.000'' SP0.125'' SP0.250'' SP0.375'' SP0.500'' SP0.625'' SP0.750'' SP0.875'' SP1.000'' SP1.250'' SP1.500'' SP1.750'' SP2.000'' SP2.250'' SP2.500'' SP
1/40.261692CFM1011964913857796728651556433
Sones16.116.015.815.014.413.713.112.712.3
1/30.351868CFM111610741029980927871809746660
Sones17.917.617.317.216.916.516.015.815.4
1/20.522131CFM1274123611991157111410681021968913784632
Sones21.021.021.021.021.020.019.819.519.218.918.4
3/40.792450CFM1464143213991366132912921253121211701077980849716
Sones25.025.025.024.024.024.025.024.024.023.022.022.023.0
11.052693CFM161015801550152114891455142113861349127211881099989869717
Sones29.028.028.028.027.027.028.029.028.027.026.025.024.026.029.0

Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (BHP) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type B: Free inlet hemispherical fan sone levels.

Agency Compliance

Dayton Electric Mfg. Co. certifies that the blowers shown herein are licensed to bear the AMCA seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 and comply with the requirements of the AMCA Certified Ratings Program.

AMCA Sound & Air
Agency Compliance
UL/cUL 705
Agency Compliance