DaytonRound Combination Fire/Smoke Damper

Dayton round fire/smoke dampers are designed for use in HVAC system applications where emergency fire/smoke control is required. Each damper comes standard with a 165ºF fusible link and factory installed actuator. Upon temperature elevation in emergency fire smoke situations, dynamic damper closes automatically to prevent the spread of fire and smoke. Includes factory installed actuator. Qualified to UL Standard 555 as a 11/2 hour fire damper and UL Standard 555S leakage class of II.

Agency ComplianceAgency Compliance

Product Specifications (Glossary)

Agency Compliance [?]
  • UL 555
  • UL 555S
Construction [?]Galvanized Steel
Damper Diameter [?]5 7/8 in
Depth [?]15 5/8 in
Duct Diameter [?]6 in
Frame Material [?]Galvanized Steel
Free Area [?]0.16 ft2
Fusible Link Temperature [?]165 °F
Includes [?]
  • 24 Volt-Factory Mounted & Wired Actuator
  • Resetable, reusable fusible link (165ºF)
Max Velocity [?]3000 ft/min
Model DescriptionRound Combination Fire/Smoke Damper
Standards [?]
  • UL Standard 555
  • UL Standard 555S
  • IBC
  • CFSM
  • NYC MEA
TypeClass II Leakage